GE Fanuc|IC200ALG262|15 Bit Differential Current Input
GE Fanuc IC200ALG262 Module - 15 Bit Differential Current Input
Description
GE Fanuc IC200ALG262 is an 8-channel analog current input module with 15-bit resolution, designed for GE Versamax systems.
Features
- 8 differential analog input channels in one group
- Backplane-powered operation – no external power required
- Supports 4–20mA and 0–20mA input ranges
- Jumper-selectable current ranges
- LED indicators for power and status
- Detects field power loss and open-wire faults (4–20mA mode only)
- Provides 8 words of analog input data to CPU or NIU
Technical Specifications
- Number of Channels: 8 differential, single group
- Current Input Ranges: 4–20 mA, 0–20 mA (jumper configurable)
- Voltage Input Range: -10 to +10 V DC
- Resolution: 15-bit
- Update Rate: 7.5 ms per 8-channel group
- Input Filter Response: Not applicable
- Power Consumption: 200 mA from +5V backplane bus
- Wiring Requirement: Shielded twisted pair cable
-
Shield Grounding Options:
- Preferred: Ground at source device
- Alternative: Ground at I/O module via auxiliary I/O terminal
-
Fault Detection:
- Field power loss alarm
- Per-channel open-wire detection (4–20mA mode only)
GE Fanuc|IC200ALG262|15 Bit Differential Current Input



GE Fanuc|IC200ALG262|15 Bit Differential Current Input
GE Fanuc IC200ALG262 Module - 15 Bit Differential Current Input
Description
GE Fanuc IC200ALG262 is an 8-channel analog current input module with 15-bit resolution, designed for GE Versamax systems.
Features
- 8 differential analog input channels in one group
- Backplane-powered operation – no external power required
- Supports 4–20mA and 0–20mA input ranges
- Jumper-selectable current ranges
- LED indicators for power and status
- Detects field power loss and open-wire faults (4–20mA mode only)
- Provides 8 words of analog input data to CPU or NIU
Technical Specifications
- Number of Channels: 8 differential, single group
- Current Input Ranges: 4–20 mA, 0–20 mA (jumper configurable)
- Voltage Input Range: -10 to +10 V DC
- Resolution: 15-bit
- Update Rate: 7.5 ms per 8-channel group
- Input Filter Response: Not applicable
- Power Consumption: 200 mA from +5V backplane bus
- Wiring Requirement: Shielded twisted pair cable
-
Shield Grounding Options:
- Preferred: Ground at source device
- Alternative: Ground at I/O module via auxiliary I/O terminal
-
Fault Detection:
- Field power loss alarm
- Per-channel open-wire detection (4–20mA mode only)