ICS T7488 / T7488A Monitored Guarded Output Modules

Description
ICS T7488 / T7488A are 16-channel guarded output modules designed for 120 VDC load control, featuring fault tolerance, line monitoring, and TÜV certification for high-risk applications.

Features

  • 16 guarded outputs in two groups of eight
  • Fault-tolerant with parallel module configuration
  • Hot-replaceable with automatic testing
  • Detects open and short circuits
  • Front panel LEDs for status and faults
  • TÜV certified to Risk Class 5

Technical Specifications

Output Configuration

  • 16 circuits
  • Two groups of eight
  • Minimum isolation: 2500 V between field/logic and groups

Voltage and Current

  • Voltage Range: 95–140 VDC
  • Load Current:
    • 1.0 A at 0–40°C
    • 0.75 A at 60°C
  • Minimum Load:
    • 35 mA (T7488)
    • 5 mA (T7488A)
  • On-State Voltage Drop: ≤ 2.0 V
  • Surge Current:
    • 3.5 A peak
    • 3 A for 20 ms (inductive loads)
  • Output Leakage:
    • T7488: 5.5 mA (single), 8.5 mA (dual)
    • T7488A: 700 µA (single), 1 mA (dual)

Fusing

  • 2 A, 250 V fast-acting (3AB)
  • Littelfuse 322-002
  • Per output

Timing

  • Turn-On/Off Delay: 0.5 ms
  • Output Test Duration:
    • 250 ms
    • Up to 425 ms with switch fault in dual mode

Power and Dissipation

  • Safetybus Power: 1.5 load units
  • Heat Dissipation: 27 W / 92 BTUs/hr

Environmental

  • Operating Temperature: 0–60°C
  • Storage Temperature: -40–85°C
  • Humidity: 0–95%, non-condensing

Mechanical

  • Vibration: 10–55 Hz, ±0.15 mm
  • Shock: 15 g, 11 ms
  • Dimensions:
    • 12.6" H × 1.27" W × 10.12" D
    • 320 × 32 × 257 mm
  • Weight: 4.2 lbs (1.8 kg)

Certifications

  • TÜV certified to DIN V VDE 0801, Risk Class 5
  • Complies with UL 508 and CSA 22.2 No. 142-M1981

Electromagnetic Compatibility

  • Electrostatic Discharge: 6 kV (IEC 801-2, Level 3)
  • Radiated Fields: 10 V/m, 27–500 MHz (IEC 801-3, Level 3)
  • Transients/Bursts: 2 kV, 2.5 kHz (IEC 801-4, Level 4)
  • Surge Immunity:
    • 2.5 kV damped 1 MHz sine wave
    • 4 kV impulse (ANSI/IEEE C37.90)
Informação sobre Pedidos e Garantias

Termos de Compra e Devoluções

Diretrizes detalhadas sobre quantidade mínima de pedido, prazos de entrega, opções de pagamento, garantia e políticas de devolução.

Aceitamos pedidos em grandes quantidades, com quantidade mínima de pedido de apenas uma unidade.

Mediante solicitação, podemos fornecer todos os documentos necessários, incluindo Certificados de Origem/Conformidade e outros documentos de exportação necessários.

Aceitamos pagamento de 100% T/T (transferência telegráfica) antes do envio. Para itens com prazo de entrega, é necessário um depósito antecipado de 30%, sendo os 70% restantes pagos antes do envio. Para transferências em RMB, entre em contato conosco se tiver um agente na China.

Todos os itens novos e originais vêm com garantia padrão de um ano. Para opções de garantia estendida, sinta-se à vontade para entrar em contato conosco para obter detalhes de preços.

Priorizamos a sua satisfação. Se precisar devolver um item, isso deverá ser feito no prazo de 30 dias após a compra. O produto deve estar sem uso, fechado e em sua embalagem original, incluindo todos os acessórios. Os reembolsos serão processados ​​dentro de 5 a 7 dias úteis após o recebimento da devolução. Observe que as despesas de envio e manuseio não são reembolsáveis.

Comparação de Produto