Yokogawa RS-EL56 Safety Relay Module

SKU: RS-EL56
  • Manufacturer: Yokogawa

  • Product No.: RS-EL56

  • Condition:In stock

  • Product Type: Safety Relay Modules

  • Product Origin: Japan

  • Payment:T/T, Western Union

  • Weight: 850g

  • Shipping port: Xiamen

  • Warranty: 12 months

The Yokogawa RS-EL56, also cataloged as the RS-EL56 Safety Relay Module, operates as a dedicated hardware component for fail-safe contact execution and critical trip switching within ProSafe-RS safety instrumented systems. Certified to SIL3 functional safety standards under IEC 61508, the unit processes logic commands from Safety Control Units to actuate up to 16 dry-contact relay output channels, driving interlocks and final control elements operating on a 24 VDC voltage rail.

Hardware Specifications

Parameter Specification
Model RS-EL56
Brand Yokogawa
Origin Japan
Weight Standard Chassis Weight (Approx. 0.85 kg)
Dimensions Standard ProSafe-RS Module Profile
Operating Temp -20 to 60 deg C
Power Consumption Rated Voltage: 24 VDC
Output Type Dry-Contact Relay Outputs
Channel Capacity 8 or 16 Channels (Up to 256 I/O System Capacity)
Safety Level SIL3 Certified (IEC 61508, ANSI/ISA 84)
Onboard Processing 10 MHz Processor, 64 KB RAM, 32 KB EPROM
Analog / Pulse Sampling 1 Hz - 100 kHz (Accuracy: +/-0.01% FS)
Reliability Metric MTTF > 100,000 Hours
Protocol Support Modbus, ASCII, RTU
System Compatibility ProSafe-RS Safety Instrumented Systems, CENTUM DCS

Field Signal Routing & DCS Loop Integration

The RS-EL56 incorporates deterministic output drive logic tailored for critical shutdown loops and safety instrumented functions. Engineered to maintain transparent signal paths and strict channel-to-channel isolation, the module prevents parasitic crosstalk and voltage spikes from propagating back into the safety controller architecture. Galvanic isolation barriers across all active output paths ensure that 4-20 mA HART loop protocol signals and low-voltage digital interlocks connected across shared field marshalling panels operate without electrical interference.

Frequently Asked Questions

Q: How does the SIL3 certification on the RS-EL56 affect safety loop design?

A: The SIL3 rating per IEC 61508 verifies that the RS-EL56 meets probability of failure on demand (PFD) targets for high-integrity safety instrumented functions when used in Emergency Shutdown (ESD) configurations.

Q: Can the RS-EL56 exchange field diagnostic data with external SCADA software via serial protocols?

A: Yes, the hardware supports Modbus RTU and ASCII serial communication protocols, allowing external supervisory hosts to poll diagnostic state bits without impacting primary safety logic execution.

Field Installation Guidelines

  1. Power Isolation: De-energize the 24 VDC primary power feed and external field load voltages before inserting, wiring, or servicing the module.
  2. Module Socket Mounting: Seat the RS-EL56 squarely into its designated slot in the ProSafe-RS terminal base or rack chassis, pressing firmly until top and bottom locking levers snap into place.
  3. Contact Wiring Terminations: Terminate dry-contact load conductors at the removable terminal block, ensuring current loads do not exceed rated contact capacities to prevent contact degradation.
  4. Inductive Suppression: Install external flywheel diodes across DC inductive loads or RC snubbers across AC loads driven by the relay outputs to protect contacts from arc erosion.
  5. Cabinet Functional Grounding: Verify the enclosure frame and module rack backplane ground lugs connect directly to the cabinet functional earth bus with a low-impedance copper strap.
Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison