Honeywell MC-TAIH04 High-Level Analog Input Module

SKU: MC-TAIH04
  • Manufacturer: Honeywell

  • Product No.: MC-TAIH04

  • Condition:In stock

  • Product Type: Analog Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 800g

  • Shipping port: Xiamen

  • Warranty: 12 months

The Honeywell MC-TAIH04 serves as the primary MC-TAIH04 High-Level Analog Input Module utilized to execute high-density signal acquisition and analog-to-digital conversion across Honeywell TotalPlant Solution (TPS) platforms.

Hardware Specifications

Parameter Specification
Model MC-TAIH04
Brand Honeywell
Origin USA
Weight 0.8 kg
Dimensions 12.7 cm x 4.5 cm x 15.7 cm
Operating Temp -20 deg C to 60 deg C
Power Consumption Standard backplane draw
Channel Capacity 16 analog input channels
Supported Signal Types 4-20 mA current loops, 1-5 VDC voltage, HART-enabled digital signals
System Architecture Honeywell TPS / TDC 3000 I/O bus
Signal Processing High-accuracy multiplexed A/D conversion

Cold Junction Compensation and Loop Protocol Performance

Designed to directly interface field transmitters with process managers, the card processes up to 16 differential analog loops. Channel-to-channel isolation networks prevent electrical noise and ground potential shifts from affecting adjacent channels or degrading backplane data transfers. Integrated cold junction compensation (CJC) references maintain micro-volt precision across varying ambient enclosure temperatures, ensuring that 4-20 mA HART signal pass-through remains stable during continuous system operation.

Frequently Asked Questions

Q: Does the MC-TAIH04 support direct pass-through of HART digital diagnostic data?

A: Yes, the onboard signal conditioning circuitry allows HART digital FSK modulation overlay signals to pass transparently to compatible I/O processors without stripping the primary 4-20 mA analog value.

Q: How is field wiring connected to the MC-TAIH04 input module?

A: The card slots into the rack assembly and interfaces to field sensors via a dedicated Field Termination Assembly (FTA) cable connected to the edge connector header.

Field Installation Guidelines

Align the module circuit board with the chassis card guides and push firmly until the backplane connector fully seats into the I/O rack header. Fasten top and bottom retaining screws to prevent vibration-induced disalignment. Ground all incoming transmitter cable shields at the panel single-point grounding bus. Keep low-voltage instrument cabling isolated from high-voltage AC lines by maintaining a minimum separation distance of 300 mm within wire ducts.

Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison