Honeywell CC-TAIL51 Input Modules

SKU: CC-TAIL51
  • Manufacturer: Honeywell

  • Product No.: CC-TAIL51

  • Condition:In stock

  • Product Type: Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

The Honeywell CC-TAIL51 , also cataloged as the CC-TAIL51 LLAI IOTA Module, operates as a dedicated hardware component for 16-channel low-level analog input signal termination within Honeywell Experion PKS platforms.

Hardware Specifications

Parameter Specification
Model CC-TAIL51
Brand Honeywell
Origin USA
Weight Standard Series C IOTA Weight
Dimensions 9 in (229 mm) length
Operating Temp -40 deg C to +70 deg C
Power Consumption Passive backplane loop powered / 24 VDC
Channel Capacity 16 Channels
Module Integration Supports CC-TUIO51 and CC-TUIO41 modules
Configuration Type Low Level Analog Input (LLAI) Non-Redundant

Field Loop Signaling & Channel Isolation

The CC-TAIL51 termination assembly incorporates high-density circuit routing designed to preserve low-level analog signal integrity across all 16 input channels. Engineered to maintain channel-to-channel isolation, the board prevents ground loops and electrical interference from degrading thermocouple and millivolt sensor measurements. It supports bi-directional 4-20 mA HART loop protocol routing and passes high-frequency digital instrument diagnostics directly to connected CC-TUIO51 and CC-TUIO41 processing units without signal attenuation.

Frequently Asked Questions

Q: Which I/O processing modules are electrically compatible with the CC-TAIL51 baseboard?

A: The CC-TAIL51 assembly is specifically designed to interface directly with CC-TUIO51 and CC-TUIO41 universal input/output modules.

Q: Is the CC-TAIL51 configured for redundant module mounting?

A: No, the CC-TAIL51 is a single-slot, non-redundant Low Level Analog Input (LLAI) Input Output Termination Assembly (IOTA).

Field Installation Guidelines

  1. Isolate all 24 VDC external loop power feeds prior to securing or removing the 9-inch assembly on the mounting channel.
  2. Fasten the base plate to the cabinet carrier frame using dedicated retention screws to maintain a metallic ground path to chassis earth.
  3. Route field input sensor cables through designated wire channels, bonding shield drain wires to the main cabinet grounding bar.
  4. Check pin alignment carefully before seating the CC-TUIO51 or CC-TUIO41 module onto the card-edge connector to prevent terminal strain.
Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison