Allen-Bradley 1769-OB16P CompactLogix Solid-State Output Module

SKU: 1769-OB16P
  • Manufacturer: Allen-Bradley

  • Product No.: 1769-OB16P

  • Condition:In stock

  • Product Type: PLC Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 260g

  • Shipping port: Xiamen

  • Warranty: 12 months

Designed for high-density 24V DC discrete control applications within CompactLogix and MicroLogix architectures, the Allen-Bradley 1769-OB16P (1769-OB16P Protected Solid-State DC Output Module) provides reliable digital signal execution for industrial automation systems.

Specifications Matrix & Suffix Comparison

Feature / Model 1769-OB16P 1769-OB16 1769-OB8
Output Channels 16 Sourcing 16 Sourcing 8 Sourcing
Electronic Protection Integrated Short-Circuit & Overcurrent Protection Fuse Protection Recommended Fuse Protection Recommended
Max Current per Point (30 °C / 60 °C) 1.0 A / 0.5 A 0.5 A / 0.5 A 1.0 A / 0.5 A
Max Current per Module (30 °C / 60 °C) 8.0 A / 4.0 A 4.0 A / 4.0 A 8.0 A / 4.0 A
Voltage Category 24V DC Sourcing (20.4–26.4V DC) 24V DC Sourcing (20.4–26.4V DC) 24V DC Sourcing (20.4–26.4V DC)

Hardware Specifications

Parameter Specification
Model 1769-OB16P
Brand Allen-Bradley
Series 1769 Compact I/O
Weight 0.56 lbs (0.26 kg)
Dimensions 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in)
Operating Temperature 0 to 60 °C (32 to 140 °F)
Output Type / Configuration Solid-State DC Sourcing Output
Number of Outputs 16 Outputs (1 Group of 16)
Operating Voltage Range 20.4 to 26.4 VDC (Nominal 24 VDC)
Backplane Current Draw 160 mA @ 5.1 VDC
Heat Dissipation 2.69 W
Continuous Current per Point 1.0 A @ 30 °C (86 °F) / 0.5 A @ 60 °C (140 °F)
Continuous Current per Module 8.0 A @ 30 °C (86 °F) / 4.0 A @ 4.0 A @ 60 °C (140 °F)
Surge Current 2.0 A for 10 ms (repeatable every 1 s)
Output Delay Time OFF to ON: 1.0 ms / ON to OFF: 2.0 ms
OFF-State Leakage Current Max 1.0 mA @ 26.4 VDC
Minimum ON-State Current 1.0 mA
On-State Voltage Drop Max 0.5 VDC
Protection Type Integrated Electronic Short Circuit / Overcurrent Protection; IEC Class 2 reinforced insulation (75 VDC continuous)
Terminal Block / Accessories 1769-RTB18 Removable Terminal Block, 1769-RL1 Door Label, 1769-RD Door
Power Supply Distance Rating 8 Modules
Wire Size (Solid / Stranded) 22 to 14 AWG solid / 22 to 16 AWG stranded

Integrated Electronic Overcurrent Protection and Deterministic Execution

The 1769-OB16P features built-in electronic short-circuit and thermal overcurrent protection for each output point, safeguarding internal solid-state switches and field wiring from temporary line faults or inductive surges without requiring external fuses. The module processes fast ON/OFF switching times (1.0 ms ON, 2.0 ms OFF) to maintain deterministic performance and precise control synchronization over the 1769 backplane bus in high-speed machinery environments.

Frequently Asked Questions

Q: What is the primary difference between the 1769-OB16 and the 1769-OB16P?

A: The "P" suffix denotes built-in electronic overcurrent and short-circuit protection, as well as higher point current capability (up to 1.0 A per point at 30 °C compared to 0.5 A max on standard 1769-OB16).

Q: Which removable terminal block is required for field wiring connection?

A: The 1769-OB16P utilizes the 18-pin 1769-RTB18 Removable Terminal Block kit.

Q: Can the 1769-OB16P module be located more than 8 slots away from the power supply?

A: No. The power supply distance rating is 8 modules. To place output modules further along the bank, an expansion power supply (such as the 1769-PA2, 1769-PB2, 1769-PA4, or 1769-PB4) must be installed.

Field Installation Guidelines

  1. Mount the module onto a 35 mm DIN rail or directly to a panel backplate using M4 screws. Ensure the DIN rail is bonded to functional earth (FE).
  2. Install the module within 8 slot positions of the primary system power supply or an expansion power supply.
  3. Completely de-energize the 24V DC field supply and system backplane power prior to attaching or removing the 1769-RTB18 terminal block.
  4. Wire field output loads using 22 to 14 AWG solid or 22 to 16 AWG stranded copper wire, maintaining tight, secure terminal connections (torque to 0.68 Nm / 6 in-lbs).
  5. Fasten the module lock levers securely to ensure proper 1769 backplane bus continuity before restoring power to the assembly.
Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.