ICS Triplex |T7488|Monitored Guarded Output Modules

SKU: T7488
  • Manufacturer: ICS Triplex

  • Product No.: T7488

  • Condition:En stock

  • Product Type: Monitored Guarded Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

ICS T7488 / T7488A Monitored Guarded Output Modules

Description
ICS T7488 / T7488A are 16-channel guarded output modules designed for 120 VDC load control, featuring fault tolerance, line monitoring, and TÜV certification for high-risk applications.

Features

  • 16 guarded outputs in two groups of eight
  • Fault-tolerant with parallel module configuration
  • Hot-replaceable with automatic testing
  • Detects open and short circuits
  • Front panel LEDs for status and faults
  • TÜV certified to Risk Class 5

Technical Specifications

Output Configuration

  • 16 circuits
  • Two groups of eight
  • Minimum isolation: 2500 V between field/logic and groups

Voltage and Current

  • Voltage Range: 95–140 VDC
  • Load Current:
    • 1.0 A at 0–40°C
    • 0.75 A at 60°C
  • Minimum Load:
    • 35 mA (T7488)
    • 5 mA (T7488A)
  • On-State Voltage Drop: ≤ 2.0 V
  • Surge Current:
    • 3.5 A peak
    • 3 A for 20 ms (inductive loads)
  • Output Leakage:
    • T7488: 5.5 mA (single), 8.5 mA (dual)
    • T7488A: 700 µA (single), 1 mA (dual)

Fusing

  • 2 A, 250 V fast-acting (3AB)
  • Littelfuse 322-002
  • Per output

Timing

  • Turn-On/Off Delay: 0.5 ms
  • Output Test Duration:
    • 250 ms
    • Up to 425 ms with switch fault in dual mode

Power and Dissipation

  • Safetybus Power: 1.5 load units
  • Heat Dissipation: 27 W / 92 BTUs/hr

Environmental

  • Operating Temperature: 0–60°C
  • Storage Temperature: -40–85°C
  • Humidity: 0–95%, non-condensing

Mechanical

  • Vibration: 10–55 Hz, ±0.15 mm
  • Shock: 15 g, 11 ms
  • Dimensions:
    • 12.6" H × 1.27" W × 10.12" D
    • 320 × 32 × 257 mm
  • Weight: 4.2 lbs (1.8 kg)

Certifications

  • TÜV certified to DIN V VDE 0801, Risk Class 5
  • Complies with UL 508 and CSA 22.2 No. 142-M1981

Electromagnetic Compatibility

  • Electrostatic Discharge: 6 kV (IEC 801-2, Level 3)
  • Radiated Fields: 10 V/m, 27–500 MHz (IEC 801-3, Level 3)
  • Transients/Bursts: 2 kV, 2.5 kHz (IEC 801-4, Level 4)
  • Surge Immunity:
    • 2.5 kV damped 1 MHz sine wave
    • 4 kV impulse (ANSI/IEEE C37.90)
Información de pedido y garantía

Condiciones de compra y devoluciones

Directrices detalladas sobre cantidad mínima de pedido, tiempos de entrega, opciones de pago, garantía y políticas de devolución.

Aceptamos con gusto pedidos al por mayor, con una cantidad mínima de pedido de solo una unidad.

Si lo solicita, podemos proporcionar todos los documentos necesarios, incluidos certificados de origen/conformidad y otros trámites de exportación requeridos.

Aceptamos pago 100% T/T (Transferencia Telegráfica) antes del envío. Para artículos con plazos de entrega, se requiere un depósito del 30 % por adelantado y el 70 % restante se debe pagar antes del envío. Para transferencias en RMB, contáctenos si tiene un agente en China.

Todos los artículos nuevos y originales vienen con una garantía estándar de un año. Para opciones de garantía extendida, no dude en contactarnos para obtener detalles sobre precios.

Priorizamos su satisfacción. Si necesita devolver un artículo, debe hacerlo dentro de los 30 días posteriores a la compra. El producto debe estar sin usar, sin abrir y en su embalaje original, incluidos todos los accesorios. Los reembolsos se procesarán dentro de los 5 a 7 días hábiles posteriores a la recepción de la devolución. Tenga en cuenta que los gastos de envío y manipulación no son reembolsables.

Comparación de productos