{"product_id":"yokogawa-f3yd64-1p-transistor-output-module","title":"Yokogawa F3YD64-1P Transistor Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eF3YD64-1P\u003c\/strong\u003e is a high-density NPN transistor output module designed by Yokogawa for the FA-M3 Range-Free Multi-Controller system. Featuring 64 sink-type output points, this module connects controllers to field actuators, relays, and indicators. The output points are organized into groups of 8 points per common line, utilizing photocoupler isolation to separate external signal lines from internal logic circuits.\u003c\/p\u003e\n\u003ch3\u003eElectrical Isolation and Circuit Protection\u003c\/h3\u003e\n\u003cp\u003eTo prevent noise propagation and protect control hardware, the module maintains a dielectric withstand voltage of 1500 V AC for one minute between its external connection terminals and internal circuitry. Each output group operates across a nominal 12 to 24 V DC load voltage range with an allowable operating range of 10.2 to 26.4 V DC. Built-in short-circuit protection safeguards the channel circuitry against accidental overcurrent conditions.\u003c\/p\u003e\n\u003ch3\u003ePower and Mechanical Specifications\u003c\/h3\u003e\n\u003cp\u003eThe module draws 275 mA from the internal 5 V DC system backplane and requires an external field power supply rated at 12 to 24 V DC (95 mA). Designed with a compact footprint measuring 2.89 cm × 8.32 cm × 10 cm and weighing 0.13 kg, the unit mounts directly into standard FA-M3 base slots.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eF3YD64-1P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eTransistor Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Points\u003c\/td\u003e\n\u003ctd\u003e64\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Line Type\u003c\/td\u003e\n\u003ctd\u003e8 points\/common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Method\u003c\/td\u003e\n\u003ctd\u003ePhotocoupler isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWithstanding Voltage\u003c\/td\u003e\n\u003ctd\u003e1500 V AC for 1 minute (external terminals to internal circuit)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Load Voltage\u003c\/td\u003e\n\u003ctd\u003e12 to 24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage Range\u003c\/td\u003e\n\u003ctd\u003e10.2 to 26.4 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInternal Current Consumption\u003c\/td\u003e\n\u003ctd\u003e275 mA (5 V DC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Power Supply\u003c\/td\u003e\n\u003ctd\u003e12 to 24 V DC, 95 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L × W × H)\u003c\/td\u003e\n\u003ctd\u003e2.89 cm × 8.32 cm × 10 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.13 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What output logic type is used by the F3YD64-1P module?\u003c\/p\u003e\n\u003cp\u003eA: The F3YD64-1P utilizes NPN sink-type transistor output logic with built-in short-circuit protection.\u003c\/p\u003e\n\u003cp\u003eQ: How are the 64 channels grouped for wiring and common connections?\u003c\/p\u003e\n\u003cp\u003eA: The 64 output channels are partitioned into 8-point groups, with each group sharing an independent common line.\u003c\/p\u003e\n\u003cp\u003eQ: What are the external power supply requirements for field-side circuit operation?\u003c\/p\u003e\n\u003cp\u003eA: The module requires an external field power supply of 12 to 24 V DC drawing up to 95 mA.\u003c\/p\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":52982655254808,"sku":"F3YD64-1P","price":210.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/F3YD64-1P3_Cocoai_c0dbcdcf-b3b4-4a79-9e16-8c0b648cbbd6.jpg?v=1792633995","url":"https:\/\/www.innoplcsync.com\/products\/yokogawa-f3yd64-1p-transistor-output-module","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}