{"product_id":"tsxdez08a4-schneider-electric-discrete-input-modules","title":"TSXDEZ08A4 | Schneider Electric Discrete Input Modules","description":"\u003cp\u003eThe \u003cstrong\u003eTSXDEZ08A4\u003c\/strong\u003e is an 8-channel capacitive discrete input module for the Modicon TSX Micro automation platform. It reads 100...120 V AC input signals (85...132 V range) at 47...63 Hz and supports 2-wire proximity sensors under IEC 1131-2 Type 2. Field wiring connects directly via screw terminals.\u003c\/p\u003e\n\u003ch3\u003eSignal Thresholds and Frequency Behavior\u003c\/h3\u003e\n\u003cp\u003eNominal input current is 11 mA at 50 Hz and 13 mA at 60 Hz across a 47...63 Hz operating frequency band. State 1 is guaranteed at \u0026gt;= 74 V and \u0026gt;= 6 mA, while state 0 is guaranteed at \u0026lt; 20 V and \u0026lt;= 4 mA.\u003c\/p\u003e\n\u003cp\u003eTransition response depends on both direction and line frequency. State 0 to state 1 takes 11...18 ms at 50 Hz and 9...16 ms at 60 Hz, while state 1 to state 0 takes 11...24 ms at 50 Hz and 10...22 ms at 60 Hz.\u003c\/p\u003e\n\u003ch3\u003ePower and Isolation\u003c\/h3\u003e\n\u003cp\u003eThe module draws 20 mA with a power consumption of 1.7 W. Isolation voltage is rated at 1500 V AC for 1 s, and net module weight is 0.23 kg.\u003c\/p\u003e\n\u003cp\u003eCapacitive input circuitry paired with IEC 1131-2 Type 2 thresholds suits AC switching signals and 2-wire proximity sensors while limiting false triggering from minor leakage.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTSXDEZ08A4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Series\u003c\/td\u003e\n\u003ctd\u003eModicon TSX Micro automation platform\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDiscrete input module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Discrete Inputs\u003c\/td\u003e\n\u003ctd\u003e8, screw terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Input Type\u003c\/td\u003e\n\u003ctd\u003eCapacitive\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Input Voltage\u003c\/td\u003e\n\u003ctd\u003e100...120 V AC (85...132 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Input Frequency\u003c\/td\u003e\n\u003ctd\u003e47...63 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Input Current\u003c\/td\u003e\n\u003ctd\u003e11 mA at 50 Hz; 13 mA at 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eState 1 Threshold\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;= 74 V; \u0026gt;= 6 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eState 0 Threshold\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 20 V; \u0026lt;= 4 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time (0 to 1)\u003c\/td\u003e\n\u003ctd\u003e11...18 ms at 50 Hz; 9...16 ms at 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time (1 to 0)\u003c\/td\u003e\n\u003ctd\u003e11...24 ms at 50 Hz; 10...22 ms at 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Compatibility\u003c\/td\u003e\n\u003ctd\u003e2-wire proximity sensor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eIEC 1131-2 Type 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e1.7 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e1500 V AC, 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.23 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What AC voltage and frequency range does the TSXDEZ08A4 accept? A: It is rated for 100...120 V AC inputs within an 85...132 V voltage span and 47...63 Hz line frequency. State 1 is guaranteed at \u0026gt;= 74 V and \u0026gt;= 6 mA, and state 0 at \u0026lt; 20 V and \u0026lt;= 4 mA.\u003c\/p\u003e\n\u003cp\u003eQ: How does line frequency affect the input response time? A: Response time varies slightly between 50 Hz and 60 Hz operation. Switching from state 0 to state 1 takes 11...18 ms at 50 Hz versus 9...16 ms at 60 Hz, and state 1 to state 0 takes 11...24 ms at 50 Hz versus 10...22 ms at 60 Hz.\u003c\/p\u003e\n\u003cp\u003eQ: What field sensors and wiring termination does this module use? A: It uses screw terminals for 8 capacitive discrete inputs and supports 2-wire proximity sensors compliant with IEC 1131-2 Type 2.\u003c\/p\u003e","brand":"SCHNEIDER","offers":[{"title":"Default Title","offer_id":53344519586072,"sku":"TSXDEZ08A4","price":179.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/TSXDEY32D3K.png?v=1795058046","url":"https:\/\/www.innoplcsync.com\/products\/tsxdez08a4-schneider-electric-discrete-input-modules","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}