{"product_id":"schneider-electric-140cps52400c-modicon-quantum-power-supply-module","title":"Schneider Electric 140CPS52400C Modicon Quantum Power Supply Module","description":"\u003cp\u003eThe \u003cstrong\u003e140CPS52400C\u003c\/strong\u003e is a redundant DC power supply module for the Modicon Quantum automation platform, converting a nominal 125 VDC input into a 5.1 VDC output rated at 8 A in redundant operation. It features Humiseal 1A33 conformal coating, internal overvoltage and overload protection, a green PWR OK indicator, and FM Class 1 Division 2 certification.\u003c\/p\u003e\n\u003ch3\u003ePower Input, Output, and Protection\u003c\/h3\u003e\n\u003cp\u003eThe input accepts 125 VDC (100 to 150 VDC range) with a typical current draw of 500 mA at 125 VDC and a 28 A inrush current at 125 VDC. It tolerates up to 1 ms of input power interruption and requires a 2 A slow-blow associated fuse.\u003c\/p\u003e\n\u003cp\u003eOn the output side, it delivers 5.1 VDC at 8 A in a redundant configuration, backed by internal overvoltage and overload protection. Power dissipation follows 6 + (1.5 x Iout) watts, where Iout is output current in amperes, and a green LED indicates PWR OK status.\u003c\/p\u003e\n\u003ch3\u003eEnvironmental, Mechanical, and Compliance\u003c\/h3\u003e\n\u003cp\u003eHumiseal 1A33 conformal coating protects the circuit assembly in humid environments up to 95 % relative humidity without condensation. Operating ratings cover 0 deg C to +60 deg C and altitudes up to 5000 m, with storage temperatures from -40 deg C to +85 deg C.\u003c\/p\u003e\n\u003cp\u003eThe standard-format module has a net weight of 0.65 kg and package dimensions of 4.5 cm x 16.5 cm x 31.5 cm (915.0 g). It carries CE marking along with UL 508, CSA C22.2 No 142, cUL, and FM Class 1 Division 2 approvals, plus IEC 801-2 ESD (4 kV contact, 8 kV air) and IEC 801-3 RF immunity (10 V\/m, 80 to 2000 MHz).\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e140CPS52400C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange of Product\u003c\/td\u003e\n\u003ctd\u003eModicon Quantum automation platform\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003ePower supply module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Type\u003c\/td\u003e\n\u003ctd\u003eRedundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e125 VDC (100 to 150 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e500 mA at 125 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e28 A at 125 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Input Power Interruption\u003c\/td\u003e\n\u003ctd\u003e1 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated Fuse Rating\u003c\/td\u003e\n\u003ctd\u003e2 A, slow-blow\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage\u003c\/td\u003e\n\u003ctd\u003e5.1 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current\u003c\/td\u003e\n\u003ctd\u003e8 A redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Overvoltage Protection\u003c\/td\u003e\n\u003ctd\u003eInternal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Overload Protection\u003c\/td\u003e\n\u003ctd\u003eInternal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e6 + (1.5 x Iout) W (Iout in A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal Signalling\u003c\/td\u003e\n\u003ctd\u003e1 LED (green) for power (PWR OK)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMarking\u003c\/td\u003e\n\u003ctd\u003eCE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications \u0026amp; Standards\u003c\/td\u003e\n\u003ctd\u003eUL 508, CSA C22.2 No 142, cUL, FM Class 1 Division 2, IEC 801-2, IEC 801-3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eConformal coating Humiseal 1A33\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e95 % without condensation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003eless than or equal to 5000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Format\u003c\/td\u003e\n\u003ctd\u003eStandard\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.65 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePackage Dimensions\u003c\/td\u003e\n\u003ctd\u003e4.5 cm x 16.5 cm x 31.5 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePackage Weight\u003c\/td\u003e\n\u003ctd\u003e915.0 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What are the key input and output electrical ratings of the 140CPS52400C? A: It operates from a 125 VDC supply (100 to 150 VDC) drawing 500 mA at 125 VDC with a 28 A inrush current, and outputs 5.1 VDC at 8 A in redundant mode. Use a 2 A slow-blow fuse on the input circuit and verify your DC source stays within 100 to 150 VDC.\u003c\/p\u003e\n\u003cp\u003eQ: How is power dissipation calculated and monitored on the 140CPS52400C? A: Power dissipation is calculated as 6 + (1.5 x Iout) watts, with Iout in amperes. A green PWR OK LED on the module provides local power status indication.\u003c\/p\u003e\n\u003cp\u003eQ: What environmental limits and certifications apply to this module? A: It is rated for 0 deg C to +60 deg C operation, -40 deg C to +85 deg C storage, up to 95 % non-condensing humidity, and altitudes up to 5000 m, with Humiseal 1A33 conformal coating and FM Class 1 Division 2 certification. Confirm that panel temperature and hazardous-location requirements match these specifications before installation.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":53440022479128,"sku":"140CPS52400C","price":270.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/140DDO35301_1d27176e-6453-41cc-b8d3-225f2a3c2a7a.png?v=1795682827","url":"https:\/\/www.innoplcsync.com\/products\/schneider-electric-140cps52400c-modicon-quantum-power-supply-module","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}