{"product_id":"output-module-allen-bradley-1746-ov32","title":"Output Module | Allen-Bradley 1746-OV32","description":"\u003cp\u003eThe \u003cstrong\u003eAllen-Bradley 1746-OV32\u003c\/strong\u003e is a 32-point digital DC sinking output module designed for the SLC 500 programmable controller platform. It provides 24 VDC nominal output operation, with a supported voltage range of 5-50 VDC. The module features two groups of 16 outputs, a maximum continuous module current of 8 A, and support for local or remote I\/O configurations.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eOutput Configuration and Electrical Characteristics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe 1746-OV32 uses a sinking output configuration, in which the output circuit switches the connected load toward the DC common reference. This arrangement requires compatible field wiring and a suitable external DC supply for the connected loads.\u003c\/p\u003e\n\u003cp\u003eThe module provides 32 output points divided into two electrically organized groups of 16. Each output supports a continuous current of 0.50 A at 30 deg C, decreasing to 0.25 A at 60 deg C. The total continuous current per module is rated at 8 A, subject to the applicable operating conditions.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1746-OV32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eSLC 500\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital DC Sinking Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eDigital DC Sinking Output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Outputs\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Configuration\u003c\/td\u003e\n\u003ctd\u003e2 groups of 16 outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Output Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e5-50 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eContinuous Output Current at 30 deg C\u003c\/td\u003e\n\u003ctd\u003e0.50 A per point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eContinuous Output Current at 60 deg C\u003c\/td\u003e\n\u003ctd\u003e0.25 A per point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eContinuous Current per Module\u003c\/td\u003e\n\u003ctd\u003e8 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Current per Point\u003c\/td\u003e\n\u003ctd\u003e1.0 A for 10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Repetition at 30 deg C\u003c\/td\u003e\n\u003ctd\u003eEvery 1 second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Repetition at 60 deg C\u003c\/td\u003e\n\u003ctd\u003eEvery 2 seconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Delay, OFF-to-ON\u003c\/td\u003e\n\u003ctd\u003e0.1 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Delay, ON-to-OFF\u003c\/td\u003e\n\u003ctd\u003e1.0 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Current\u003c\/td\u003e\n\u003ctd\u003e190 mA at 5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Isolation Voltage\u003c\/td\u003e\n\u003ctd\u003e1500 VAC for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermal Dissipation per Channel\u003c\/td\u003e\n\u003ctd\u003e0.172 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectronic Output Protection\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eOne-slot SLC 500 chassis installation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eI\/O Installation\u003c\/td\u003e\n\u003ctd\u003eLocal or Remote\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection Type\u003c\/td\u003e\n\u003ctd\u003e40-pin female connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWiring Options\u003c\/td\u003e\n\u003ctd\u003e1746-NC3; 1492-CABLExx with 1492-IFM40xx\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.19 lbs (0.54 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGTIN \/ UPC\u003c\/td\u003e\n\u003ctd\u003e10662468092910\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between the 1746-OV32 and a sourcing output module?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The 1746-OV32 uses sinking output circuitry, which switches the output toward the DC common reference. A sourcing output module instead supplies positive voltage to the connected load. The field wiring and load connection arrangement must match the output configuration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the 1746-OV32 drive loads requiring 0.50 A continuously?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Each output point supports 0.50 A at 30 deg C, but this rating decreases to 0.25 A at 60 deg C. The total continuous current for the module is rated at 8 A. Both the individual channel and total module limits must be observed.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the 1746-OV32 provide built-in electronic output protection?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: No. The supplied specifications identify the module as having no electronic output protection. External circuit protection should be provided and selected according to the connected loads and wiring requirements.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":53357189202200,"sku":"1746-OV32","price":270.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/1746-OV82_Cocoai_1_10c60041-7f94-4bcf-b252-5eeb3abe9601.jpg?v=1795140140","url":"https:\/\/www.innoplcsync.com\/products\/output-module-allen-bradley-1746-ov32","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}