{"product_id":"honeywell-mc-taih02-field-termination-assemblies","title":"Honeywell MC-TAIH02 Field Termination Assemblies","description":"\u003cdiv class=\"qk-md-paragraph\"\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell MC-TAIH02\u003c\/strong\u003e serves as the primary \u003cstrong\u003eMC-TAIH02\u003c\/strong\u003e High-Level Analog Input\/STI Field Termination Assembly (FTA) utilized to execute high-level analog and Smart Transmitter Interface (STI) signal termination across Honeywell Process Manager I\/O platforms. The 16-channel assembly acts as the physical interface bridge between field instrumentation and control processors. By accommodating phone connector-style terminations, the board ensures reliable signal routing and electrical conditioning for process variables before they are digitized on the system I\/O bus.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eBase Model\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003ePrefix \/ Suffix\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eMC\u003c\/td\u003e\n\u003ctd\u003eModule Category\u003c\/td\u003e\n\u003ctd\u003eProcess Manager Component Series\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTAIH\u003c\/td\u003e\n\u003ctd\u003eTechnical Function\u003c\/td\u003e\n\u003ctd\u003eTermination Assembly Input High-Level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e02\u003c\/td\u003e\n\u003ctd\u003eRevision \/ Hardware Variant\u003c\/td\u003e\n\u003ctd\u003e16-Channel High-Level Analog \u0026amp; STI Phone-Connector Configuration\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMC-TAIH02\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.50 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard Field Termination Assembly footprint\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePassive termination board (powered via I\/O processor link)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Types\u003c\/td\u003e\n\u003ctd\u003eHigh-level analog (4-20 mA \/ 1-5 VDC) or STI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination Style\u003c\/td\u003e\n\u003ctd\u003ePhone connector-style\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProcessor Compatibility\u003c\/td\u003e\n\u003ctd\u003eMC-PAIH03, MC-PSTX03, MU-PSTX03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e4-20 mA HART Loop Protocol and STI Connectivity\u003c\/h3\u003e\n\u003cp\u003eDesigned to interface directly with advanced process architectures, the Honeywell MC-TAIH02 accommodates both standard 4-20 mA HART loop protocol instruments and dedicated Smart Transmitter Interface (STI) protocols. Its internal trace topology incorporates channel-to-channel isolation features that prevent transient differential noise from corrupting digital communication superimposed on the analog signal. Onboard filtering networks maintain signal integrity for high-speed digital communications, ensuring uninterrupted data exchange between field transmitters and compatible MC-PAIH03, MC-PSTX03, or MU-PSTX03 processors.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Which Honeywell I\/O processors are directly compatible with the MC-TAIH02 FTA?\u003c\/p\u003e\n\u003cp\u003eA: The MC-TAIH02 is engineered for direct interconnectivity with Honeywell MC-PAIH03, MC-PSTX03, and MU-PSTX03 I\/O processors using standard interface cables.\u003c\/p\u003e\n\u003cp\u003eQ: How are field instruments wired to the MC-TAIH02 board?\u003c\/p\u003e\n\u003cp\u003eA: Connections to field sensors and smart transmitters are made via phone connector-style terminals designed for rapid, secure locking and physical strain relief.\u003c\/p\u003e\n\u003cp\u003eQ: Can the MC-TAIH02 process Smart Transmitter Interface (STI) and standard analog signals simultaneously on different channels?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the board architecture supports input channel configurations for both standard high-level analog signals (such as 4-20 mA \/ 1-5 VDC) and digital STI transmitter signals based on the assigned processor mode.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eVerify that the mounting rack or cabinet panel is fully de-energized before mounting the FTA board to prevent accidental short circuits.\u003c\/li\u003e\n\u003cli\u003eSecure the MC-TAIH02 onto the standard marshaling rack baseplate using the specified mounting screws.\u003c\/li\u003e\n\u003cli\u003ePlug the multi-conductor I\/O interface cable firmly into the board's system connector, ensuring the retaining latches click into place.\u003c\/li\u003e\n\u003cli\u003eInsert field wiring plugs into the phone connector-style terminals, verifying that all conductor pins are correctly aligned and fully seated.\u003c\/li\u003e\n\u003cli\u003eLand cable shield wires directly on the cabinet single-point ground bus bar to ensure maximum immunity against industrial electromagnetic noise.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003c\/div\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52783228125464,"sku":"MC-TAIH02","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/MU-TAIH02_1_c785ca6e-d056-4a29-ab5b-44476575742e.png?v=1790584284","url":"https:\/\/www.innoplcsync.com\/products\/honeywell-mc-taih02-field-termination-assemblies","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}