{"product_id":"honeywell-cc-paoh01-experion-series-c-hart-analog-output-module","title":"Honeywell CC-PAOH01 Experion Series C HART Analog Output Module","description":"\u003cp\u003eThe Honeywell \u003cstrong\u003eCC-PAOH01\u003c\/strong\u003e is a 16-channel high-level analog output module designed for the Experion PKS control platform. It converts digital control signals into standard 4–20 mA current outputs with integrated HART protocol support, enabling bidirectional digital communication with smart field instruments like valve positioners and transmitters. This module features extensive self-diagnostics, per-channel safe-state configuration, and optional redundancy to ensure high availability in demanding process control loops.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-PAOH01\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eHART Analog Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eExperion PKS Series C I\/O\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e16 Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Range\u003c\/td\u003e\n\u003ctd\u003e4–20 mA DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Communication\u003c\/td\u003e\n\u003ctd\u003eHART Protocol\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current Linearity\u003c\/td\u003e\n\u003ctd\u003e$\\pm0.05\\%$ of Full Scale nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Resistive Load\u003c\/td\u003e\n\u003ctd\u003e800 Ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time\u003c\/td\u003e\n\u003ctd\u003e$\\le80$ ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Current Consumption\u003c\/td\u003e\n\u003ctd\u003e0.46 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.01 lbs (0.46 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eArchitecture and Functional Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eHART Protocol Integration\u003c\/strong\u003e: Combines traditional 4–20 mA control signals with superimposed digital communication, allowing remote configuration, device calibration, and continuous health monitoring of smart field instruments directly from the control system.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfigurable Fail-Safe Behavior\u003c\/strong\u003e: Supports customizable FAILOPT parameters on a per-channel basis, enabling outputs to hold their last value or shed to a predefined safe state upon a controller or communication fault.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundancy Support\u003c\/strong\u003e: Compatible with redundant IOTA (Input\/Output Termination Assembly) options, ensuring bumpless switchover and uninterrupted loop control during module maintenance or fault conditions.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What termination assemblies are compatible with the CC-PAOH01 module?\u003c\/p\u003e\n\u003cp\u003eA: It can be paired with non-redundant IOTAs such as CC-TAOX01 or redundant IOTAs like CC-TAOX11 and CC-GAOX11 depending on system architecture requirements.\u003c\/p\u003e\n\u003cp\u003eQ: How does the module handle open-circuit detection?\u003c\/p\u003e\n\u003cp\u003eA: The module includes internal diagnostic features that perform output readback and trigger discrepancy or open-wire alarms if loop continuity is disrupted.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":49415859142936,"sku":"CC-PAOH01","price":251.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/CC-PAOH01.jpg?v=1733192033","url":"https:\/\/www.innoplcsync.com\/products\/honeywell-cc-paoh01-experion-series-c-hart-analog-output-module","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}