{"product_id":"honeywell-80366195-100-mu-taih22-terminal-adapter","title":"Honeywell 80366195-100 MU-TAIH22 Terminal Adapter","description":"\u003cdiv class=\"qk-md-paragraph qk-md-has-multi-modal\"\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell 80366195-100\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eMU-TAIH22\u003c\/strong\u003e Analog Input \/ STI Function Terminal Adapter, operates as a dedicated hardware component for 16-channel high-level analog signal acquisition and signal processing within Honeywell Total Building Management (TBM) and process automation systems. It interfaces field instrumentation, transmitters, and sensors directly to controller sub-assemblies while providing redundant Smart Transmitter Interface (STI) outputs for fault-tolerant telemetry.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eModel Code Segment\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eIdentifier \/ Suffix\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eTechnical Description\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBase Model\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMU-TAIH22\u003c\/td\u003e\n\u003ctd\u003eHigh-level Analog Input \/ STI Function Terminal Adapter chassis\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePart Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e80366195-100\u003c\/td\u003e\n\u003ctd\u003eHardware ordering assembly code for 16-channel configuration\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Class\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTAIH\u003c\/td\u003e\n\u003ctd\u003eHigh-level Analog Input processing (4-20 mA, 0-10 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInterface Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e22 Suffix\u003c\/td\u003e\n\u003ctd\u003eDual redundant STI bus output termination sub-assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMU-TAIH22\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e80366195-100\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.8 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e192 x 145 x 27 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePassive \/ system powered via termination bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Compatibility\u003c\/td\u003e\n\u003ctd\u003e4-20 mA, 0 to 10 VDC high-level analog\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 high-level analog inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e10 Mohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Performance\u003c\/td\u003e\n\u003ctd\u003e12-bit resolution, +\/-0.1% full-scale accuracy\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSTI Output\u003c\/td\u003e\n\u003ctd\u003eRedundant 0 to 5 VDC, 10 mA max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e4-20 mA HART Loop Protocol \u0026amp; Channel-to-Channel Isolation\u003c\/h3\u003e\n\u003cp\u003eThe 80366195-100 MU-TAIH22 adapter provides channel-to-channel isolation and low-pass RC filtering across all 16 high-level analog input channels. High input impedance (10 Mohm) prevents loading errors on 4-20 mA current loops and 0-10 VDC voltage transmitters. Dedicated primary-to-secondary galvanic separation isolates field-side wiring loops from backplane logic networks, preventing electrical cross-talk, common-mode noise propagation, and ground loop current feedback from corrupting digitizer conversion cycles.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the MU-TAIH22 adapter process both 4-20 mA current loops and 0-10 VDC voltage signals simultaneously?\u003c\/p\u003e\n\u003cp\u003eA: Yes, each of the 16 channels accommodates high-level analog inputs (4-20 mA or 0-10 VDC) based on terminal jumper configurations and input impedance conditioning built into the adapter.\u003c\/p\u003e\n\u003cp\u003eQ: How does the redundant STI output function during primary signal channel degradation?\u003c\/p\u003e\n\u003cp\u003eA: The dual STI output channels drive parallel 0-5 VDC signal paths, maintaining active telemetry feedback to downstream processors if one STI communication leg experiences signal degradation or physical line failure.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eCabinet Mounting \u0026amp; Thermal Environment\u003c\/strong\u003e: Secure the 192 x 145 x 27 mm adapter housing onto standard panel DIN rails within a protective IP54 enclosure. Maintain a minimum vertical spacing of 50 mm above and below the housing to facilitate thermal convection across the -40 to +70 deg C operating range.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShielding \u0026amp; Wiring Routing\u003c\/strong\u003e: Route all 4-20 mA and 0-10 VDC field wiring in shielded twisted-pair cables away from AC power conductors and switching inductive loads. Connect cable drain shields to the panel protective earth ground bus at a single point to protect internal signal paths.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Block Termination\u003c\/strong\u003e: Strip field conductor insulation to 7 mm before securing wire ends into the screw terminal blocks. Apply a maximum tightening torque of 0.5 Nm to maintain stable electrical contact without stressing internal circuit board traces.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52688917889304,"sku":"80366195-100 MU-TAIH22","price":75.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/MU-TAIH02_1_ef7db810-26aa-42e5-be3a-7e8ad8055504.png?v=1789544412","url":"https:\/\/www.innoplcsync.com\/products\/honeywell-80366195-100-mu-taih22-terminal-adapter","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}