{"product_id":"experion-dc-output-module-honeywell-tc-odd321","title":"Experion DC Output Module | Honeywell TC-ODD321","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell TC-ODD321\u003c\/strong\u003e is a 32-channel digital output module designed for the Experion Process Knowledge System (PKS) C200 and C300 controller platforms. It provides 24 VDC solid-state switching for field actuators, indication lamps, relays, and solenoids in continuous industrial control applications. The module features two isolated groups of 16 output channels, reducing field wiring complexity while providing structured common connections.\u003c\/p\u003e\n\u003ch3\u003eOutput Performance and Voltage Derating\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eTC-ODD321\u003c\/strong\u003e operates across a voltage range of 10 VDC to 31.2 VDC at ambient temperatures up to 50 deg C, with linear derating to 28 VDC at 60 deg C. Each output point supports a minimum load current of 3.0 mA, ensuring stable switching for high-impedance control loads. Maximum on-state voltage drop is restricted to 1.0 VDC at rated current, minimizing signal loss across field loops.\u003c\/p\u003e\n\u003ch3\u003eCircuit Protection and Wiring Interface\u003c\/h3\u003e\n\u003cp\u003eTo handle inductive inrush loads, each output channel supports repeatable surge currents up to 1.0 A for 10 ms at 60 deg C. The module interfaces with field cabling using the dedicated \u003cstrong\u003eTC-TBCH\u003c\/strong\u003e 36-position removable terminal block. Total thermal dissipation is rated at 6.1 W under full operating conditions.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTC-ODD321\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Output Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Count\u003c\/td\u003e\n\u003ctd\u003e32 outputs (2 groups of 16 points per common)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e10 to 31.2 VDC (up to 50 deg C); 10 to 28 VDC (at 60 deg C)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-State Voltage Drop\u003c\/td\u003e\n\u003ctd\u003e1.0 VDC max at rated current (3.0 VDC per IEC 61131-2)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum On-State Load\u003c\/td\u003e\n\u003ctd\u003e3.0 mA per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Current\u003c\/td\u003e\n\u003ctd\u003e1.0 A for 10 ms per point (repeatable every 2 s at 60 deg C)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e6.1 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Block Model\u003c\/td\u003e\n\u003ctd\u003eTC-TBCH (36-position)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Weight\u003c\/td\u003e\n\u003ctd\u003e1.5 kg (3.3 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What removable terminal block is required for wiring the TC-ODD321? A: The module requires the Honeywell \u003cstrong\u003eTC-TBCH\u003c\/strong\u003e 36-position terminal block for field wiring connection and signal isolation between the two 16-point groups.\u003c\/p\u003e\n\u003cp\u003eQ: How does temperature affect the output voltage range of this module? A: The module operates at full output rating up to 31.2 VDC at 50 deg C. Above 50 deg C, the maximum allowable voltage derates linearly to 28 VDC at 60 deg C.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":49471032295704,"sku":"TC-ODD321","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0892\/3483\/3688\/files\/fcv.jpg?v=1767062497","url":"https:\/\/www.innoplcsync.com\/products\/experion-dc-output-module-honeywell-tc-odd321","provider":"InnoPLC Sync Co., Ltd.","version":"1.0","type":"link"}