GE Fanuc IC694MDL930 is an 8-point isolated relay output module for the RX3i PACSystems, featuring normally-open contacts for switching AC/DC loads.
Features
Provides 8 individually isolated relay outputs with separate commons.
Supports mixed voltage operation: 24 VDC, 120/240 VAC nominal.
Enables point-to-point and field-to-backplane isolation.
Reports reliable switching for industrial load control.
Compatible with standard I/O slots in RX3i PLC racks.
Technical Specifications
- Number of Outputs: 8 (isolated, Form A)
- Nominal Voltages: 24 VDC, 120/240 VAC
-
Operating Voltage Range:
- 5 to 30 VDC
- 5 to 250 VAC (50–60 Hz)
-
Maximum Output Current:
- 4 A resistive per point
- 2 A pilot duty per point
- 20 A maximum total per module (UL)
- Minimum Load: 10 mA per point
- Inrush Current: 5 A maximum
- Response Time: ≤ 15 ms (On and Off)
- Voltage Drop: Not specified
-
Isolation:
- Field to backplane and frame ground: 250 VAC continuous, 1500 VAC for 1 minute
- Point-to-point: 250 VAC continuous, 1500 VAC for 1 minute
GE Fanuc|IC694MDL930|8-Point Isolated Relay Output Module
GE Fanuc|IC694MDL930|8-Point Isolated Relay Output Module
GE Fanuc IC694MDL930 8-Point Isolated Relay Output Module
Description
GE Fanuc IC694MDL930 is an 8-point isolated relay output module for the RX3i PACSystems, featuring normally-open contacts for switching AC/DC loads.
Features
Provides 8 individually isolated relay outputs with separate commons.
Supports mixed voltage operation: 24 VDC, 120/240 VAC nominal.
Enables point-to-point and field-to-backplane isolation.
Reports reliable switching for industrial load control.
Compatible with standard I/O slots in RX3i PLC racks.
Technical Specifications
- Number of Outputs: 8 (isolated, Form A)
- Nominal Voltages: 24 VDC, 120/240 VAC
-
Operating Voltage Range:
- 5 to 30 VDC
- 5 to 250 VAC (50–60 Hz)
-
Maximum Output Current:
- 4 A resistive per point
- 2 A pilot duty per point
- 20 A maximum total per module (UL)
- Minimum Load: 10 mA per point
- Inrush Current: 5 A maximum
- Response Time: ≤ 15 ms (On and Off)
- Voltage Drop: Not specified
-
Isolation:
- Field to backplane and frame ground: 250 VAC continuous, 1500 VAC for 1 minute
- Point-to-point: 250 VAC continuous, 1500 VAC for 1 minute