ICS Triplex |T7488|Monitored Guarded Output Modules

SKU: T7488
  • Manufacturer: ICS Triplex

  • Product No.: T7488

  • Condition:En stock

  • Product Type: Monitored Guarded Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

ICS T7488 / T7488A Monitored Guarded Output Modules

Description
ICS T7488 / T7488A are 16-channel guarded output modules designed for 120 VDC load control, featuring fault tolerance, line monitoring, and TÜV certification for high-risk applications.

Features

  • 16 guarded outputs in two groups of eight
  • Fault-tolerant with parallel module configuration
  • Hot-replaceable with automatic testing
  • Detects open and short circuits
  • Front panel LEDs for status and faults
  • TÜV certified to Risk Class 5

Technical Specifications

Output Configuration

  • 16 circuits
  • Two groups of eight
  • Minimum isolation: 2500 V between field/logic and groups

Voltage and Current

  • Voltage Range: 95–140 VDC
  • Load Current:
    • 1.0 A at 0–40°C
    • 0.75 A at 60°C
  • Minimum Load:
    • 35 mA (T7488)
    • 5 mA (T7488A)
  • On-State Voltage Drop: ≤ 2.0 V
  • Surge Current:
    • 3.5 A peak
    • 3 A for 20 ms (inductive loads)
  • Output Leakage:
    • T7488: 5.5 mA (single), 8.5 mA (dual)
    • T7488A: 700 µA (single), 1 mA (dual)

Fusing

  • 2 A, 250 V fast-acting (3AB)
  • Littelfuse 322-002
  • Per output

Timing

  • Turn-On/Off Delay: 0.5 ms
  • Output Test Duration:
    • 250 ms
    • Up to 425 ms with switch fault in dual mode

Power and Dissipation

  • Safetybus Power: 1.5 load units
  • Heat Dissipation: 27 W / 92 BTUs/hr

Environmental

  • Operating Temperature: 0–60°C
  • Storage Temperature: -40–85°C
  • Humidity: 0–95%, non-condensing

Mechanical

  • Vibration: 10–55 Hz, ±0.15 mm
  • Shock: 15 g, 11 ms
  • Dimensions:
    • 12.6" H × 1.27" W × 10.12" D
    • 320 × 32 × 257 mm
  • Weight: 4.2 lbs (1.8 kg)

Certifications

  • TÜV certified to DIN V VDE 0801, Risk Class 5
  • Complies with UL 508 and CSA 22.2 No. 142-M1981

Electromagnetic Compatibility

  • Electrostatic Discharge: 6 kV (IEC 801-2, Level 3)
  • Radiated Fields: 10 V/m, 27–500 MHz (IEC 801-3, Level 3)
  • Transients/Bursts: 2 kV, 2.5 kHz (IEC 801-4, Level 4)
  • Surge Immunity:
    • 2.5 kV damped 1 MHz sine wave
    • 4 kV impulse (ANSI/IEEE C37.90)
Informations sur la commande et la garantie

Conditions d'achat et de retour

Des directives détaillées sur la quantité minimale de commande, les délais de livraison, les options de paiement, la garantie et les politiques de retour.

Nous acceptons volontiers les commandes groupées, avec une quantité minimum de commande d’une seule unité.

Sur demande, nous pouvons fournir tous les documents nécessaires, y compris les certificats d'origine/conformité et autres documents d'exportation requis.

Nous acceptons le paiement 100% T/T (transfert télégraphique) avant l'expédition. Pour les articles avec des délais de livraison, un acompte de 30 % est requis à l'avance, les 70 % restants étant payables avant expédition. Pour les transferts en RMB, veuillez nous contacter si vous avez un agent en Chine.

Tous les articles neufs et originaux bénéficient d’une garantie standard d’un an. Pour les options de garantie prolongée, n'hésitez pas à nous contacter pour plus de détails sur les prix.

Nous priorisons votre satisfaction. Si vous devez retourner un article, cela doit être fait dans les 30 jours suivant l'achat. Le produit doit être inutilisé, non ouvert et dans son emballage d'origine, y compris tous les accessoires. Les remboursements seront traités dans les 5 à 7 jours ouvrables suivant la réception du retour. Veuillez noter que les frais d'expédition et de manutention ne sont pas remboursables.

Comparaison de produits