Honeywell RM7840E1016 7800 Series Relay Module

SKU: RM7840E1016
  • Manufacturer: Honeywell

  • Product No.: RM7840E1016

  • Condition:In stock

  • Product Type: Burner Control Relay Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

The Honeywell RM7840E1016 is a microprocessor-based burner control relay module designed for automatically fired gas, oil, or combination fuel single-burner applications. Operating as part of the 7800 Series system, this programming control provides automatic burner sequencing, flame supervision, system status indication, and self-diagnostics to ensure safe ignition and continuous monitoring during operation.

Functional Features and Operation

This module integrates precise timing functions to optimize combustion safety and operational control. Features include user-selectable airflow check functionality, a 15-second post-purge cycle, pre-ignition verification, and a 5-second early spark termination sequence. It supports interrupted pilot arrangements alongside interrupted second-stage pilot valve timing, ensuring defined fuel-ignition timing during startup.

System Components and Enclosure

The assembly includes a protective dust cover to shield internal electronic components from industrial contamination. The relay module mounts directly onto a standard 7800 Series wiring subbase, requiring a plug-in flame signal amplifier and a purge card to establish complete burner management capability.

Specifications

Parameter Specification
Model RM7840E1016
Brand Honeywell
Product Type Burner Control Relay Module
Series 7800 Series
Pilot Type Interrupted pilot
Second Stage Pilot Interrupted second-stage pilot valve
Early Spark Termination 5 seconds
Post Purge Time 15 seconds
Airflow Check User selectable
Weight 3.00 lbs

Frequently Asked Questions

Q: What additional components are required to operate the RM7840E1016? A: The module requires a compatible 7800 Series wiring subbase, a plug-in purge card to set pre-purge timing, and a plug-in flame signal amplifier selected for the specific flame detector in use.

Q: How does the early spark termination feature function during burner ignition? A: Early spark termination cuts off the direct ignition spark 5 seconds before the main fuel valve period expires, allowing the system to verify pilot stability prior to main flame establishment.

Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison