Honeywell|8U-TAOXA1|Analog Output IOTA Module
HONEYWELL 8U-TAOXA1 Analog Output IOTA Module
Description
The HONEYWELL 8U-TAOXA1 is a single-slot analog output module of the IOTA series, providing configurable high-level output signals for control of field devices in Experion PKS and TPS systems.
The HONEYWELL 8U-TAOXA1 is a single-slot analog output module of the IOTA series, providing configurable high-level output signals for control of field devices in Experion PKS and TPS systems.
Features
- Single-ended analog output with standard industrial ranges
- IOTA-based design for direct field wiring
- Supports voltage or current output per channel
- Integrated diagnostics and calibration support
Technical Specifications
- Output Type: Analog (current or voltage)
- Signal Range: 4–20 mA or 0–10 V DC (field-selectable)
- Load Capability: Up to 750 Ω at 20 mA (for current output)
- Output Accuracy: ±0.1% of full scale
- Resolution: 16-bit D/A conversion
- Update Rate: ≤100 ms per channel
- Isolation: 500 VDC between system and field circuits
- Operating Temperature: –20°C to +70°C
- Power Supply: Powered by IOPS unit
- Backplane Interface: IOHIGHWAY at 1.2 Mbit/s or 4 Mbit/s
Honeywell|8U-TAOXA1|Analog Output IOTA Module
Current product
Current
Vendor:
Honeywell
Honeywell|8U-TAOXA1|Analog Output IOTA Module
Regular price
$100.00
Sale price
$100.00
Regular price
$300.00
Options
Descriptions
HONEYWELL 8U-TAOXA1 Analog Output IOTA Module
Description
The HONEYWELL 8U-TAOXA1 is a single-slot analog output module of the IOTA series, providing configurable high-level output signals for control of field devices in Experion PKS and TPS systems.
The HONEYWELL 8U-TAOXA1 is a single-slot analog output module of the IOTA series, providing configurable high-level output signals for control of field devices in Experion PKS and TPS systems.
Features
- Single-ended analog output with standard industrial ranges
- IOTA-based design for direct field wiring
- Supports voltage or current output per channel
- Integrated diagnostics and calibration support
Technical Specifications
- Output Type: Analog (current or voltage)
- Signal Range: 4–20 mA or 0–10 V DC (field-selectable)
- Load Capability: Up to 750 Ω at 20 mA (for current output)
- Output Accuracy: ±0.1% of full scale
- Resolution: 16-bit D/A conversion
- Update Rate: ≤100 ms per channel
- Isolation: 500 VDC between system and field circuits
- Operating Temperature: –20°C to +70°C
- Power Supply: Powered by IOPS unit
- Backplane Interface: IOHIGHWAY at 1.2 Mbit/s or 4 Mbit/s