الأوصاف
A cost-effective draw-out type protection system for small to medium generators, integrating protection, monitoring, metering, and advanced communications. Features 5A phase CT inputs (P5), low-range control power (LO: 20-60V DC/20-48V AC), 4-20mA analog outputs (A20), and enhanced LCD display (E) for real-time monitoring.
- Comprehensive generator protection: stator differential, 100% stator ground, loss of excitation, reverse power, etc.
- Advanced monitoring: 12 RTD inputs for thermal protection, 4 analog inputs for vibration, high-accuracy metering for power parameters.
- Flexible communications: RS232, RS485, 10BaseT Ethernet; supports Modbus RTU/TCP, DNP 3.0.
- User-friendly interface: large sunlight-readable display, LED indicators, keypad for local configuration.
- Draw-out design for minimal downtime during maintenance.
-
Current Inputs: 5A CT secondary (P5), range 0.02-20x CT, accuracy ±0.5% at <2x CT.
-
Voltage Inputs: VT ratio 1.00-240.00:1, secondary 200V AC (phase), 100V AC (neutral), accuracy ±0.5%.
-
Power Supply (LO): 20-60V DC / 20-48V AC (48-62Hz), 45VA max.
-
Analog Outputs (A20): 4-20mA, accuracy ±1%, max load 1200Ω.
-
Output Relays: 6 Form C contacts, 10A/30VDC resistive, 10A/120VAC.
-
Communications: 2x RS485 (19.2kbps), 1x RS232, 10BaseT Ethernet (Modbus/TCP, DNP 3.0).
-
Environmental: Operating temp. -40°C to +60°C, humidity up to 95% non-condensing, altitude ≤2000m.
-
Certifications: UL508, UL1053, CE, CSA, ISO9001 compliant.